Set an alert wait in Grafana
Grafana OSS 12.3.0
Start with an existing Pump temperature high rule and a working temperature feed. Initial setup is outside this lesson.
- Open Alerting → Alert rules, find Pump temperature high, and choose Edit.
- Keep the condition above 60°C and the Temperature alerts evaluation group, which evaluates every 10 seconds.
- Under Set evaluation behavior, set Pending period to 1m and save the rule.
The wait starts at the first evaluation above the limit. The demonstration’s 30-second rise stays Pending, then returns to Normal when a check no longer meets the condition. If checks keep meeting it, the rule reaches Firing on the first evaluation at or after a full minute.
The video compresses elapsed time. Pending period controls when the rule fires; notification delivery has separate settings.
Grafana 12.3 references: Rule configuration · Alert evaluation